Reducing energy consumption through chiller optimization

Hawaii Energy Systems

Project Details

Project Description

Hawaii Energy Systems (HES), a provider of smart energy management and control were asked to review the operation of an existing central plant located in a tropical climate in the South Pacific.

Tropical climates have some unique challenges and the customer was looking to improve comfort while reducing energy consumption. Due to the constant warm, humid weather in the region, cooling requirements are quite high. South Pacific Islands have some of the highest energy expense and safeguarding their occupants’ comfort is key to business productivity.

Opportunity

The client began a capital improvement program to replace their aging, inefficient chillers with three new high efficiency chillers. Working with their engineering consultant, they developed a detailed specification for a central plant optimization system to be installed that would operate the system at its optimal efficiency.

HES and Optergy teamed up to provide the custom control, optimization and reporting capabilities that the client demanded. Concerns about efficiency were hampered by lack of visibility and contextual reporting and alarms. Increasing visibility and improved performance were the desired outcomes.

Solution

The existing chilled water system (3 chillers, 3 cooling towers, primary/secondary pumping was operating at an average 1.53 kW/ton. New premium high-efficiency chillers, pumps and VFD’s were installed and controlled by the chiller’s “smart controls”.

HES implemented a central plant optimization system which uses Optergy Enterprise, a smart energy monitoring and control system.

The Optergy system provided the web-based user interface that allows users to quickly control and adjust chiller settings while viewing the active and dynamic conditions of the chiller plant. The Optergy system also generated reports and dashboard views for a quick and easy way for users to interact with the system.

$171,000 Cost Savings in First Year

Results

The existing chilled water system  consisting of 3 chillers, 3 cooling towers and primary/secondary pumping was operating at an average 1.53 kW/ton. New premium high-efficiency chillers, pumps and VFD’s were installed and controlled by the chiller’s “smart controls”. Energy demand was reduced by 21.6% to 1.20kW/ton.

HES implemented a central plant optimization system for this new equipment and over the course of the first year of operation that slashed the measured energy usage to 0.86kW/ton – a 28.3% reduction over the chiller’s control system. This equates to a total reduction in energy consumption of 628,289 kWh (or 628.3MWh) over the first 12 months.

15,649

Incandescent lamps switched to LEDs

1,844,369

Kms driven by an average family car

Our Top 3 Applications

Optergy Applications BMS

Building Management Systems

We create building automation software that can be used to monitor and control equipment and operations.

Optergy Applications EMS

Energy Management
Systems

Visually appealing real-time reporting system displays all utility performances in a
building.

Optergy Applications Tenant Billing

Tenant
Billing

Automatically generate any utility billing content for all your tenants, as well as the ability to charge for after hour usage.

Questions?